- New
Automatic voltage conditioner correcting voltage sags down to -40% and swells up to +30% phase by phase with ±1% output accuracy, plus reactive power, harmonic and unbalance compensation. 30 kVA to 500 kVA, 220 V and 400 V.
ATEX / IECEx documentation supplied where stated
Incoterms agreed in each quotation
Price, lead time and certificates in every offer
The Automatic Voltage Conditioner (AVC) combines a rectifier, an inverter, a series compensation transformer and a monitoring system. It injects a corrective voltage in series with the supply to mitigate voltage sags (down to -40%) and swells (up to +30%) without interruption, and its power electronics can also compensate reactive power, harmonics and three-phase unbalance. The load receives a stable voltage, protecting sensitive processes from costly stoppages.
Typical uses: plants sensitive to voltage dips (petrochemicals, semiconductors, pharmaceuticals, automotive, textiles), end of long low-voltage lines with low voltage and unbalance, networks with high photovoltaic penetration, and road tunnels with long supply lines and fluctuating loads.
Key features
Available models
| Model | Rated power (kVA) | System voltage (V) | Cooling |
|---|---|---|---|
| AVC-0.4-30k | 30 | 220 / 400 | Forced air |
| AVC-0.4-60k | 60 | 400 | Forced air |
| AVC-0.4-80k | 80 | 400 | Forced air |
| AVC-0.4-100k | 100 | 400 | Forced air |
| AVC-0.4-150k | 150 | 400 | Forced air |
| AVC-0.4-300k | 300 | 400 | Forced air |
| AVC-0.4-400k | 400 | 400 | Forced air |
| AVC-0.4-500k | 500 | 400 | Forced air |
Technical specifications
| Rated power | 30 kVA (220 V), 45 to 500 kVA (380 V) |
|---|---|
| Rated current | 45 A (220 V), 90 to 750 A (380 V) |
| Grid structure | L/N + PE (220 V), 3P4W + PE (380 V) |
| Input voltage range | -40% to +30% |
| Output voltage accuracy | ±1% |
| Compensation response time | < 20 ms |
| Rated frequency | 50/60 Hz (±2.5 Hz) |
| AC overload | Continuous operation at 1.1 x rated capacity |
| Functions | Voltage compensation, combined with reactive power, harmonic and (380 V) three-phase unbalance compensation |
| Harmonic compensation | ≥ 95% (3rd to 13th order), THDi ≤ 3%, THDv < 1.5% |
| Reactive power compensation | ≥ 98% |
| Unbalance compensation | ≥ 95% (380 V) |
| Compensation transformer | Dry type, laminated silicon steel core, insulation class H, temperature rise ≤ 90 K, 1.1 x continuous overload |
| Noise | ≤ 70 dB |
| Communication | RS485 (4G / Wi-Fi supported) |
| Ambient temperature | -10 to +50 °C (derated above 40 °C) |
| Altitude | < 2000 m (derated above) |
| Relative humidity | ≤ 90%, non-condensing |
| Protection degree | IP20 (IP54 on request) |
Applications
Petrochemical and chemical plants, semiconductor and pharmaceutical manufacturing, automotive and textile plants, rural and long low-voltage distribution lines, photovoltaic-rich distribution grids, traffic tunnels and remote industrial sites.
Documentation
The manufacturer datasheet is available in the attachments. Manufacturer quality, environmental and OH&S management systems certified to ISO 9001, ISO 14001 and ISO 45001. Test reports are available on request. Sizing support is available: send us your single-line diagram and measurements with your quotation request.
Supplied from a qualified manufacturer selected by ASSINOV. Origin, manufacturer details and certificates are provided with our quotation.